Inspection #: 825899
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: See Corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/1/2024TransferCorrect Below*  Dryer receptacle in bathroom shall be GFCI protected.
10/1/2024TransferCorrect Below* Back Hall outside of restroomExit sign is not functioning.
9/27/2024TransferCorrect Below* Dental equipment installed including compressor and VAC machineListings need to be verified. UPDATE: Dental chairs do not appear to have an listing from an NRTL.
9/27/2024CorrectedCorrect Below* PanelSchedule shall be updated.
9/27/2024CorrectedCorrect Below* Reception areaNorth side of reception desk area. Pony wall with 2 gang receptacles not inspected. Remove cover for inspection.
9/27/2024TransferCorrect Below* Hall 115, waiting 101No ceiling inspection for new lighting installed in these areas. Remove tiles and provide ladder for inspection. UPDATE: MC cable supported off ceiling wires. Wires shall be connected to ceiling and grid to be considered an support. In waiting 101