| Date | Status | Code | Description | Ref | Location | Comments |
| 10/1/2024 | Transfer | Correct Below | * | | | Dryer receptacle in bathroom shall be GFCI protected. |
| 10/1/2024 | Transfer | Correct Below | * | | Back Hall outside of restroom | Exit sign is not functioning. |
| 9/27/2024 | Transfer | Correct Below | * | | Dental equipment installed including compressor and VAC machine | Listings need to be verified.
UPDATE: Dental chairs do not appear to have an listing from an NRTL. |
| 9/27/2024 | Corrected | Correct Below | * | | Panel | Schedule shall be updated. |
| 9/27/2024 | Corrected | Correct Below | * | | Reception area | North side of reception desk area. Pony wall with 2 gang receptacles not inspected. Remove cover for inspection. |
| 9/27/2024 | Transfer | Correct Below | * | | Hall 115, waiting 101 | No ceiling inspection for new lighting installed in these areas. Remove tiles and provide ladder for inspection.
UPDATE: MC cable supported off ceiling wires. Wires shall be connected to ceiling and grid to be considered an support. In waiting 101 |