Inspection #: 825173
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Some corrections made- see remaining items.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/1/2026TransferCorrect Below*  1. Label available fault current and date calculated on service equipment. 2. Nvenia and Kaeser units do not appear to have a third party listing label (such as UL). Field evaluation may be required. 3. Workspace required at exterior compactor controller.
9/25/2024CorrectedCorrect Below* MDP style service disconnect portion.CEA has installed a lock on the door to the service disconnects. Remove lock to provide access to service disconnects as required by 2017 NEC 240.24(B)(1).