| Date | Status | Code | Description | Ref | Location | Comments |
| 4/1/2026 | Transfer | Correct Below | * | | | 1. Label available fault current and date calculated on service equipment.
2. Nvenia and Kaeser units do not appear to have a third party listing label (such as UL). Field evaluation may be required.
3. Workspace required at exterior compactor controller. |
| 9/25/2024 | Corrected | Correct Below | * | | MDP style service disconnect portion. | CEA has installed a lock on the door to the service disconnects. Remove lock to provide access to service disconnects as required by 2017 NEC 240.24(B)(1). |