Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 821444
Inspection Type: Plumbing Rough
Inspector: E.Huckaba
Result: Partial
Comment: Plumbing rough in for new Tub/Shower valves and new H2O lav stub outs- APPROVED. NOTES: PLUMBING FOR ROOMS 121 THROUGH 129 ONLY. OK TO COVER.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/20/2024TransferBackflowInspTested and TaggedBackflow assembly shall be tested and properly tagged- UPC 603.4.2Irrigation BP 
6/20/2024TransferPlumbRgh9PlansApproved plans must be on site  
6/20/2024TransferGasPipeComSee comments Boiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.
6/20/2024TransferGasRgh14PipingSee commentssee commentsBoiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.