Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 820239
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Approved
Comment: Electrical Install Approved TAG#41415

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/23/2024CorrectedCorrect Below*  Ground bond wire shall bond building frame, gas line, and water line.
8/23/2024CorrectedCorrect Below* Front PorchLight shall be installed at front porch.
8/23/2024CorrectedCorrect Below* ExteriorDedicated GFCI protected receptacle shall be located in front of trailer for Headbolt heater. Receptacle shall be tamper resistant and weather rated type. With an Extra Duty labeled cover.
8/23/2024CorrectedCorrect Below* Laundry areaWashing machine receptacle shall be GFCI protected.
8/23/2024CorrectedCorrect Below*  Bathroom receptacle shall be GFCI receptacle.
8/23/2024CorrectedCorrect Below*  Kitchen receptacles shall be GFCI protected: Countertop receptacles, and Dishwasher receptacle.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS