| Date | Status | Code | Description | Ref | Location | Comments |
| 8/23/2024 | Corrected | Correct Below | * | | | Ground bond wire shall bond building frame, gas line, and water line. |
| 8/23/2024 | Corrected | Correct Below | * | | Front Porch | Light shall be installed at front porch. |
| 8/23/2024 | Corrected | Correct Below | * | | Exterior | Dedicated GFCI protected receptacle shall be located in front of trailer for Headbolt heater. Receptacle shall be tamper resistant and weather rated type. With an Extra Duty labeled cover. |
| 8/23/2024 | Corrected | Correct Below | * | | Laundry area | Washing machine receptacle shall be GFCI protected. |
| 8/23/2024 | Corrected | Correct Below | * | | | Bathroom receptacle shall be GFCI receptacle. |
| 8/23/2024 | Corrected | Correct Below | * | | | Kitchen receptacles shall be GFCI protected: Countertop receptacles, and Dishwasher receptacle. |