Inspection #: 819353
Inspection Type: Plumbing Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Plumbing Rough - Approved Showerpan liner tests approved serving rms 352-270 (rms 358 & 360 have tubs), OK to cover. NOTE: Corrections remain related to boiler replacement.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/20/2024TransferBackflowInspTested and TaggedBackflow assembly shall be tested and properly tagged- UPC 603.4.2Irrigation BP 
6/20/2024TransferPlumbRgh9PlansApproved plans must be on site  
6/20/2024CorrectedGasPipeComSee comments Boiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.
6/20/2024CorrectedGasRgh14PipingSee commentssee commentsBoiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.