Inspection #: 819317
Inspection Type: Final Electrical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/17/2024 Correct Below* Interior panelsTop of panels has open raceway to attic. Ko seals required.
8/17/2024 Correct Below* Exterior lightsSome not functioning.
8/17/2024 Correct Below* Plans Do not match asbuilt onsite condition. Onsite condition has new service supplying Relocatable classrooms. Verify load calcs for feeder supplying units. Sheets show approximately 65 amps per phase for each building. Some plans appear to be duplicates from past projects. At this time, load calc and feeder configuration is unclear.