| Date | Status | Code | Description | Ref | Location | Comments |
| 8/17/2024 | Transfer | Correct Below | * | | Interior panels | Top of panels has open raceway to attic. Ko seals required. |
| 8/17/2024 | Transfer | Correct Below | * | | Exterior lights | Some not functioning. |
| 8/17/2024 | Transfer | Correct Below | * | | Plans | Do not match asbuilt onsite condition. Onsite condition has new service supplying Relocatable classrooms. Verify load calcs for feeder supplying units. Sheets show approximately 65 amps per phase for each building. Some plans appear to be duplicates from past projects. At this time, load calc and feeder configuration is unclear. |