Inspection #: 819274
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections. Electrical final conditionally approved for use of new relocatable class rooms until 8/30/24 to make corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/17/2024TransferCorrect Below* Interior panelsTop of panels has open raceway to attic. Ko seals required.
8/17/2024TransferCorrect Below* Exterior lightsSome not functioning.
8/17/2024TransferCorrect Below* Plans Do not match asbuilt onsite condition. Onsite condition has new service supplying Relocatable classrooms. Verify load calcs for feeder supplying units. Sheets show approximately 65 amps per phase for each building. Some plans appear to be duplicates from past projects. At this time, load calc and feeder configuration is unclear.