| Date | Status | Code | Description | Ref | Location | Comments |
| 8/16/2024 | Transfer | 01 | See inspection comments | | | Handle ties required at breakers on 1st floor A wing panel. |
| 8/16/2024 | Transfer | 01 | See inspection comments | | | Completed panel schedules required throughout A wing all floors. |
| 8/14/2024 | Corrected | 01 | See inspection comments | | | No power at emergency lighting on 1st and 2nd floor. |
| 8/14/2024 | Corrected | 01 | See inspection comments | | 2nd floor A wing panel. | Shared neutrals must be bundled with hots and breaker ties must be installed. Add breaker blank. |