Inspection #: 818557
Inspection Type: Electrical Rough
Inspector: O.Burbridge
Result: Correction
Comment: Electrical final approved for 2nd floor A wing and 1st floor A wing rooms 1100-1113 pending completion of noted items.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/16/2024Transfer01See inspection comments  Handle ties required at breakers on 1st floor A wing panel.
8/16/2024Transfer01See inspection comments  Completed panel schedules required throughout A wing all floors.
8/14/2024Corrected01See inspection comments  No power at emergency lighting on 1st and 2nd floor.
8/14/2024Corrected01See inspection comments 2nd floor A wing panel.Shared neutrals must be bundled with hots and breaker ties must be installed. Add breaker blank.