Inspection #: 818029
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Corrections remain. Bonding correction completed. Provide access to verify listing of equipment.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/12/2024CorrectedCorrect Below* BridgeInstall bonding jumper provided.
8/12/2024TransferCorrect Below* 1" LFMC between controller and lighting on bridge. Install LFMC per NEC, fasten and support. Max of equivalent of 4 90 degree bends allowed per run of conduit.
8/12/2024TransferCorrect Below* New gateway bridge. Provide documentation and verify listing label on control panel covers the complete bridge. Listing label on equipment appears to be for a industrial control equipment using UL standard 508A. Does not appear to cover entire piece of equipment. Provide access to verify listing of equipment.