| Date | Status | Code | Description | Ref | Location | Comments |
| 8/8/2024 | Corrected | 01 | See inspection comments | | | Room 100 requires can lights to be cut into soffit. |
| 8/8/2024 | Transfer | 01 | See inspection comments | | | Emergency light junction box on 2nd floor incomplete. |
| 8/8/2024 | Corrected | 01 | See inspection comments | | | Add dead fronts where panels are live and do not have a cover installed. |
| 8/8/2024 | Transfer | 01 | See inspection comments | | | 2nd floor conduits containing new conductors require a ground wire. |
| 8/8/2024 | Transfer | 01 | See inspection comments | | | 2nd floor conduits between gutters and panels require #10 conductors to be used where #12s are. |