Inspection #: 818005
Inspection Type: Electrical Rough
Inspector: O.Burbridge
Result: Partial
Comment: Some corrections made. Electrical final for room 100-113 approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/8/2024Corrected01See inspection comments  Room 100 requires can lights to be cut into soffit.
8/8/2024Transfer01See inspection comments  Emergency light junction box on 2nd floor incomplete.
8/8/2024Corrected01See inspection comments  Add dead fronts where panels are live and do not have a cover installed.
8/8/2024Transfer01See inspection comments  2nd floor conduits containing new conductors require a ground wire.
8/8/2024Transfer01See inspection comments  2nd floor conduits between gutters and panels require #10 conductors to be used where #12s are.