Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 817749
Inspection Type: Electrical Rough
Inspector: O.Burbridge
Result: Correction
Comment: Electrical final approved for phase 2 third floor and stairwell only.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/8/2024Transfer01See inspection comments  Room 100 requires can lights to be cut into soffit.
8/8/2024Transfer01See inspection comments  Emergency light junction box on 2nd floor incomplete.
8/8/2024Transfer01See inspection comments  Add dead fronts where panels are live and do not have a cover installed.
8/8/2024Transfer01See inspection comments  2nd floor conduits containing new conductors require a ground wire.
8/8/2024Transfer01See inspection comments  2nd floor conduits between gutters and panels require #10 conductors to be used where #12s are.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS