Inspection #: 817035
Inspection Type: Ceiling Rough Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical final approved for bathrooms 114-120. Rough approved for bathrooms in rooms 121-129.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/5/2024TransferEC1Correct Below 2nd floor east sideJunction box for emergency lighting incomplete.
8/5/2024TransferEC1Correct Below 2nd floor east sideBond gutters with largest ground wire and provide covers and end caps.
8/5/2024TransferEC1Correct Below 2nd floor east sideReplace #12 conductors in flex between gutters and panels with #10 copper conductors and add #10 ground wire.