| Date | Status | Code | Description | Ref | Location | Comments |
| 8/5/2024 | Transfer | EC1 | Correct Below | | 2nd floor east side | Junction box for emergency lighting incomplete. |
| 8/5/2024 | Transfer | EC1 | Correct Below | | 2nd floor east side | Bond gutters with largest ground wire and provide covers and end caps. |
| 8/5/2024 | Transfer | EC1 | Correct Below | | 2nd floor east side | Replace #12 conductors in flex between gutters and panels with #10 copper conductors and add #10 ground wire. |