| Date | Status | Code | Description | Ref | Location | Comments |
| 9/25/2024 | Transfer | Correct Below | * | | MDP style service disconnect portion. | CEA has installed a lock on the door to the service disconnects. Remove lock to provide access to service disconnects as required by 2017 NEC 240.24(B)(1). |
| 8/1/2024 | Corrected | Correct Below | * | | | Does voltage of service match requirements for TRUs? |
| 8/1/2024 | Transfer | Correct Below | * | | | Label service with available fault current and date calculated. |
| 8/1/2024 | Corrected | Correct Below | * | | | NEC 626.31(C) requires specific voltage/amperage ratings for receptacles. Installation does not match these requirements. Cords on TRUs do not match up with voltage, amperage, or pin configuration of installed receptacles. |
| 8/1/2024 | Corrected | Correct Below | * | | | Physical protection required at Electrified truck service and receptacle pedestals. |
| 3/4/2024 | Transfer | Correct Below | * | | | Heat trace requires labels and lockout on breaker. |
| 3/4/2024 | Transfer | Correct Below | * | | | Label disconnects with source. |
| 3/4/2024 | Transfer | Correct Below | * | | | 30" width and 36" depth workspace required at exterior compactor controller. |
| 3/4/2024 | Transfer | Correct Below | * | | | Compactor and baler require wire phasing. |
| 2/1/2024 | Transfer | Correct Below | * | | | Platform required at rooftop condensing units so that centerline of disconnect handle is no greater than 6'7" above working platform. |
| 2/1/2024 | Corrected | Correct Below | * | | | Shore power service and associated hook ups incomplete. |
| 2/1/2024 | Transfer | Correct Below | * | | | Truck plugs at loading dock incomplete. |
| 2/1/2024 | Transfer | Correct Below | * | | | Compactor disconnect requires bonding bushing. |
| 2/1/2024 | Transfer | Correct Below | * | | | Conveyor system incomplete. Not all components appear to have a valid listing label. Field evaluation by a NRTL may be required. |