Inspection #: 816236
Inspection Type: Plumbing Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Plumbing Rough - Approved DWV rough & test approve serving rms 401, 403, 405, 407, 409, 411, 413, 419, 421, 423, 425, 427, 429 & 431, OK to cover.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/25/2024CorrectedPlumbRgh12Piping SupportPiping is not properly supported- UPC Section 313.0, including Table 313.1All vertical fl-fl plumbing pipingSupport at every fl & mid story guides where required.
7/18/2024TransferPlumbRgh14CommentsSee Inspectors Comments Cleanouts required for WC and most sinks. All drain lines on 1st floor beyond 5 feet from main require a cleanout. THIS IS FOR ENTIRE FIRST FLOOR