Inspection #: 816121
Inspection Type: Underground Plumbing
Inspector: Y.Dovba
Result: Correction
Comment: Underground gas piping rough-in and test Approved. Serving 4-outdoor heaters. NOTE: Heaters not installed at this time. NOTE: Please follow previous correction regarding penetrating the footing. NOTE: All building penetrations must be done above grade and penetrations must be also be sleeved. NOTE: southeast corner of the building. corner of 4th avenue and C street. (HDPE piping).

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/30/2024TransferUnGrndPlumb11Corrections as FollowsMake corrections as followsUnderground gas piping serving outdoor patio heaters. southeast corner of the building. corner of 4th avenue and C street. (HDPE piping).Per 2018 IFGC local amendment 404.21 approved outdoor gas flexes to be installed at each end prior to entering the building proving 6'' inches of displacement.
7/30/2024TransferUnGrndPlumb11Corrections as FollowsMake corrections as followsUnderground gas piping serving outdoor patio heaters. southeast corner of the building. corner of 4th avenue and C street. (HDPE piping).Per 2018 IFGC section 404.17.1 plastic piping limitations: HDPE piping to be transitioned outside the building with a use an approved anodeless riser. (each gas outlet to be transitioned by using and anodeless riser) Per 2018 IFGC section 404.6 Gas piping must not penetrate the building/footing below grade. (above grade only)