Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 816106
Inspection Type: Service
Inspector: O.Burbridge
Result: Correction
Comment: Service approved- tag 36162. See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/30/2024TransferCorrect service item below*  Minimum 25K AIC rating required on 150A breaker.
7/30/2024CorrectedCorrect service item below*  Bond N/G at disconnects.
7/30/2024CorrectedCorrect service item below*  Bond SEC, meter base, and disconnects.
7/30/2024CorrectedCorrect service item below*  Meter requires 10" clearance from centerline of meter to other enclosures.
7/30/2024TransferCorrect service item below*  Provide labels at disconnects for load served and AFC/date calculated.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS