Inspection #: 814168
Inspection Type: Plumbing Rough
Inspector: J.Jaworski
Result: Correction
Comment: Re-inspect required

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/18/2024TransferPlumbRgh14CommentsSee Inspectors Comments Cleanouts required for WC and most sinks. All drain lines on 1st floor beyond 5 feet from main require a cleanout. THIS IS FOR ENTIRE FIRST FLOOR
7/18/2024TransferPlumbRgh14CommentsSee Inspectors Comments Hangers required for WC arms, riser clamps required for floor to floor piping, call back in inspection for 160,162,163,164,165,166.
7/18/2024TransferPlumbRgh14CommentsSee Inspectors Comments Listed transition bands required through out entire rough. Replace and re-test, call back in inspection for 160,162,163,164,165,166.