Inspection #: 812743
Inspection Type: Temp Electric
Inspector: O.Burbridge
Result: Partial
Comment: Corrections made- temp power approved. Tag 36146

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/8/2024CorrectedCorrect following Item  Service lateral conduit.Requires #1/0 copper bonding conductor from CT enclosure to grounding bushing.
7/8/2024CorrectedCorrect following Item  Gutter containing conductors supplying 50A temp receptacles.Bond at least (1) equipment ground to the gutter.