Inspection #: 812344
Inspection Type: Service
Inspector: O.Burbridge
Result: Correction
Comment: Ground rods approved. See corrections as noted.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/30/2024TransferCorrect service item below*  Minimum 25K AIC rating required on 150A breaker.
7/30/2024TransferCorrect service item below*  Bond N/G at disconnects.
7/30/2024TransferCorrect service item below*  Bond SEC, meter base, and disconnects.
7/30/2024TransferCorrect service item below*  Meter requires 10" clearance from centerline of meter to other enclosures.
7/30/2024TransferCorrect service item below*  Provide labels at disconnects for load served and AFC/date calculated.