Inspection #: 812060
Inspection Type: Plumbing Rough
Inspector: Y.Dovba
Result: Approved
Comment: 2nd portion of Med-Gas 24hr test 9:00am Oxygen and Nitrous oxide tested at 150psi, Med-Air tested at 180psi and Vacuum at 19.5 psi. NOTE: Piping serving these work stations are stubbed into the mechanical room and will be connected and inspected at a later date. NOTE: 3rd party verification report will be required by final. NOTE: Please provide me with the installers qualification.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       