| Date | Status | Code | Description | Ref | Location | Comments |
| 7/10/2024 | Transfer | Correct following Item | | | Disconnect within suction equipment. | Contractor has converted disconnecting means from factory installed cord-and-plug to toggle switch. Items requiring resolution as follows. 1. Show instructions permitting conversion from cord-and-plug to switch. 2. Fine stranded conductors require special termination devices per 110.14 - last paragraph. |
| 6/24/2024 | Transfer | Correct following Item | | | Receptacle used as equipment disconnect for teller line equipment. | Required to be GFCI protected per 210.8(B). |