Inspection #: 810015
Inspection Type: Plumbing Rough
Inspector: N.Jackson
Result: Partial
Comment: Rough and Test of built on-site shower receptors, Partial Approval. NOTE: Test includes built on-site shower receptors in rooms # 245B, 243, 242, 240, 346, 348, 351. NOTE: Built on-site shower receptor in room # 347 not tested.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/20/2024TransferBackflowInspTested and TaggedBackflow assembly shall be tested and properly tagged- UPC 603.4.2Irrigation BP 
6/20/2024TransferPlumbRgh9PlansApproved plans must be on site  
6/20/2024TransferGasPipeComSee comments Boiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.
6/20/2024TransferGasRgh14PipingSee commentssee commentsBoiler gas pipingUnion fitting required downstream of boiler isolation valves to serve each boiler per 2018 IFGC.