Inspection #: 809274
Inspection Type: Sprinkler Hydrostatic Test
Inspector: B.Meinhardt
Result: Correction
Comment: 9am if available Requested by: Jason Ando 9073889295 Jando@yukonfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/20/2024TransferFireSprkHydro4Correction(s) #2<div>Correct the following item(s):</div><div><br></div> Per Jason Ando there is something leaking by when system is at 200 PSI, they cannot find any wet spots.&nbsp; &nbsp;Further investigation of the check valves and drain valves may be need to determine if they need to be replaced.
6/20/2024TransferFireSprkHydro3Correction(s) #1<div>Correct the following item(s):</div><div><br></div> Hydrostatic test not at 200 psi as required by 2019 NFPA 13 section 28.2.1.1