Inspection #: 807609
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: See Corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/23/2024TransferCorrect Below*  Ground bond wire shall bond building frame, gas line, and water line.
8/23/2024TransferCorrect Below* Front PorchLight shall be installed at front porch.
8/23/2024TransferCorrect Below* ExteriorDedicated GFCI protected receptacle shall be located in front of trailer for Headbolt heater. Receptacle shall be tamper resistant and weather rated type. With an Extra Duty labeled cover.
8/23/2024TransferCorrect Below* Laundry areaWashing machine receptacle shall be GFCI protected.
8/23/2024TransferCorrect Below*  Bathroom receptacle shall be GFCI receptacle.
8/23/2024TransferCorrect Below*  Kitchen receptacles shall be GFCI protected: Countertop receptacles, and Dishwasher receptacle.