| Date | Status | Code | Description | Ref | Location | Comments |
| 5/24/2024 | | PlumbFinal | Comments | See Inspector Comments | The buildings mechanical room. | The buildings water main and associated piping with hose thread drains are required to have a ASSE 1011 hose connection vacuum breaker per the 2018 UPC table 603.2. |
| 5/24/2024 | Corrected | PlumbFinal | Comments | See Inspector Comments | The building water main and all associated piping. | Per the 2018 UPC 608.2. "Where the static water pressure in the water supply piping is exceeding 80 PSI an approved type pressure regulator preceded by an adequate strainer shall be installed and the static pressure reduced to 80 PSI or less. Pressure regulator(s) equal to or exceeding 1 1/2" shall not require a strainer. Such regulator(s) shall control the pressure to water outlets in the building unless otherwise approved by the Authority Having Jurisdiction. Each such regulator and strainer shall be accessibly located above ground or in a vault equipped with a properly sized and sloped bore-sighted drain to daylight, shall be protected from freezing, and shall have the strainer readily accessible for cleaning without removing the regulator or the strainer body or disconnecting the supply piping. An approved expansion tank shall be installed in the cold water distribution piping downstream of each such regulator to prevent excessive pressure from developing due to thermal expansion and to maintain the pressure setting of the regulator." |