Click Here To View Another Inspection Inspection #: 805949 Inspection Type: Plumbing Rough Inspector: Y.Dovba Result: Partial Comment: Dwv and water piping rough-in and tests Approved. Per Approved Plans M4.1 M5.0 sinks and work stations. First portion of Med-Gas 24hr test 9:00am Oxygen and Nitrous oxide tested at 150psi, Med-Air tested at 180psi and Vacuum at 19.5 psi. NOTE: Piping serving these work stations are stubbed into the mechanical room and will be connected and inspected at a later date. NOTE: 3rd party verification report will be required by final. Inspection Corrections DateStatusCodeDescriptionRefLocationComments