Inspection #: 805335
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: Supplies and furniture in place preventing proper inspection. Procedural rooms have not been electrically approved for use. Inspection was not able to complete possibly more corrections will need to be addressed. After an inspection with access to all electrical installed is provided.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/27/2024TransferCorrect Below* Dental equipment installed including compressor and VAC machineListings need to be verified.
9/27/2024TransferCorrect Below* PanelSchedule shall be updated.
9/27/2024TransferCorrect Below* Reception areaNorth side of reception desk area. Pony wall with 2 gang receptacles not inspected. Remove cover for inspection.
9/27/2024TransferCorrect Below* Hall 115, waiting 101No ceiling inspection for new lighting installed in these areas. Remove tiles and provide ladder for inspection.