Click Here To View Another Inspection Inspection #: 804706 Inspection Type: Underground Plumbing Inspector: Y.Dovba Result: Approved Comment: Complete underground dwv and water piping rough-in and tests Approved. Including trap primers. last 2-floor drains and restroom groups, end on the line clean-out. NOTE: Per 2018 UPC amendment 314.4 use clean fill when back-filling and protect piping through slab. NOTE: Per 2018 UPC section 707.4 install clean-outs at upper terminals above slab on runs exceeding 5ft horizontal runs. Inspection Corrections DateStatusCodeDescriptionRefLocationComments