Inspection #: 804678
Inspection Type: Plumbing Rough
Inspector: Y.Dovba
Result: Correction
Comment: 1st floor 2-Restroom groups dwv and water piping rough-in and test Approved. NOTE: Provide access panels at final for all valves (both restrooms) 2nd floor bar area water piping rough-in and test Approved. including trap-primer piping behind the bar wall. NOTE: Provide access panel at final for all valve (trap primer) NOTE: Correction from 3rd floor restroom hasn't been addressed (Floor drain requirement).

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/15/2024TransferPlumbRgh14CommentsSee Inspectors Comments3RD FLOOR RESTROOMSPER 2018 UPC- CHAPTER 4- PLUMBING FIXTURES AND FIXTURE FITTINGS, SECTION 418.3-LOCATION OF FLOOR DRAINS, #1- TOILET ROOMS CONTAINING TWO OR MORE WATER CLOSETS OR A COMBINATION OF 1-WATER CLOSET AND 1-URINAL, EXCEPT IN A DWELLING UNIT.