| Date | Status | Code | Description | Ref | Location | Comments |
| 6/20/2024 | Transfer | PlumbRgh14 | Comments | See Inspectors Comments | 3rd/4th fl plumbing vents | Venting undersized per 2018 UPC tables 702.1 & 703.2 |
| 6/20/2024 | Transfer | PlumbRgh12 | Piping Support | Piping is not properly supported- UPC Section 313.0, including Table 313.1 | Plastic & CI DWV | Riser clamps to serve vertical piping penetrating fl & mid story guides to serve vertical ABS. |
| 6/20/2024 | Transfer | PlumbRgh6 | Nail Plates | Nail plate(s) required-UPC 312.9 | DWV piping | |