Inspection #: 804358
Inspection Type: Retro Fire Final
Inspector: B.Meinhardt
Result: Correction
Comment: REQUESTING 1:00PM FINAL INSPECTION Requested by: Steve Sizemore V 907-830-8465 stevev@northstarfireprotection.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/30/2024TransferRetroFire12Correction(s) #3Correct the following item(s): Sprinkler heads need to be installed above kitchen hood throughout ceiling space or hood needs to be skirted to make the area separated and all non combustible.
5/30/2024TransferRetroFire9Work exceed retrofit limitsWork exceed retrofit permit limitations of AMC 23.45.105.7.28.2.5.  Apply for a full permit AMC 23.45.105.7.28.2.4.2, 23.45.105.7.28.2.4.4, 23.45.105.7.28.2.4.5 Work exceeds limits of a retro permit with the K14 extended coverage sprinkler heads.  Full permit with plans and calculations required.
5/30/2024TransferRetroFire11Correction(s) #2Correct the following item(s): Sprinkler head in southeast corner of dinning room is painted or covered in tape.
5/30/2024TransferRetroFire10Correction(s) #1Correct the following item(s): Sprinkler heads are over spaced to the new wall in dinning room - 10 feet off the wall.   Sprinkler spacing is 18x18 max per original design.  Need to add 2 heads