| Date | Status | Code | Description | Ref | Location | Comments |
| 5/30/2024 | Transfer | Correct Below | * | | | AHU 18 incomplete. |
| 11/14/2023 | Corrected | Correct Below | * | | Phase 2 staff lounge | GFCI protection for refrigerator must be readily accessible. |
| 10/26/2023 | Corrected | Correct Below | * | | | Humidifier incomplete. |
| 10/26/2023 | Corrected | Correct Below | * | | | Panelboard bonding per NEC 517.14 required. |
| 10/26/2023 | Corrected | Correct Below | * | | | Scanning equipment in nuclear medicine room 309 incomplete- being relocated from area being remodeled in phase 2. |