Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 803956
Inspection Type: Temp Electric
Inspector: O.Burbridge
Result: Correction
Comment: 1. Green #6 copper required from CT can to meter base. 2. Land all grounding electrode conductors at neutral bus on disconnect switch. 3. Bond both ends of any metallic raceways which contain grounding electrode conductors. 4. Provide change order showing new configuration for service equipment. 5. Electrical permit to be issued in electrical contractor's name. 6. Schedule reinspection when complete.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter