| 5/8/2024 | Transfer | Notes | Fire Final Notes | Fire Final Notes: | | CO by Nicole Thomson has been rescinded from 5/7/2024, do to stocking issue with clearance to fire sprinkler heads. |
| 5/8/2024 | Transfer | Fire 13 | Correction(s) #1 | Please correct the following: | | Stock is being placed up to the drop ceiling level. Stock shall remain 18 inches below the fire sprinkler defector per the requirements of the 2018 IFC 315.3.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or not less than 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.<div>:<br><div>Exceptions</div><div>:</div><div>1. The 2-foot (610 mm) ceiling clearance is not required for storage along walls in nonsprinklered areas of buildings.</div><div>2. The 18-inch (457 mm) ceiling clearance is not required for storage along walls in areas of buildings equipped with an automatic sprinkler system</div></div> |