Inspection #: 803334
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: Correction
Comment: Please call Brian Von Gunten 30 minutes before arrival Requested by: Brian Von Gunten 951-255-7398 Brianv@bauerak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/8/2024TransferNotesFire Final NotesFire Final Notes: CO by Nicole Thomson has been rescinded from 5/7/2024, do to stocking issue with clearance to fire sprinkler heads.    
5/8/2024TransferFire 13Correction(s) #1Please correct the following: Stock is being placed up to the drop ceiling level.&nbsp; &nbsp;Stock shall remain 18 inches below the fire sprinkler defector per the requirements of the 2018 IFC 315.3.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or not less than 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.<div>:<br><div>Exceptions</div><div>:</div><div>1. The 2-foot (610 mm) ceiling clearance is not required for storage along walls in nonsprinklered areas of buildings.</div><div>2. The 18-inch (457 mm) ceiling clearance is not required for storage along walls in areas of buildings equipped with an automatic sprinkler system</div></div>