Click Here To View Another Inspection Inspection #: 799941 Inspection Type: Plumbing Rough Inspector: K.Hanson Result: Partial Comment: Partial Plumbing Rough - Approved 1st portion of med gas rough & test approved serving med air, med vac & O2 serving med area w/ piping in cath lab 3 hallway each tested at 160#s, 10:15am 4-16-24. NOTE: Piping run halfway to tie in point in hallway, inspection & test required related to remaining piping prior to final tie in. Inspection Corrections DateStatusCodeDescriptionRefLocationComments