Inspection #: 799520
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Approved
Comment: Corrections made- electrical final approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/9/2024CorrectedCorrect Below*  Properly sized pull boxes or condulets required between transfer switch and generator.
4/9/2024CorrectedCorrect Electrical Below*  At generator feeders add external bond jumpers around liquidtight flex to bond rigid elbows.
4/4/2024CorrectedCorrect Below*  Provide panel schedules, labeling of AFC and date calculated at service, breaker lock for heat trace, and conduit supports.