Inspection #: 798990
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/9/2024TransferCorrect Below*  Properly sized pull boxes or condulets required between transfer switch and generator.
4/9/2024TransferCorrect Electrical Below*  At generator feeders add external bond jumpers around liquidtight flex to bond rigid elbows.
4/4/2024TransferCorrect Below*  Provide panel schedules, labeling of AFC and date calculated at service, breaker lock for heat trace, and conduit supports.