Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 798906
Inspection Type: Electrical Inspection
Inspector: E.Widman
Result: Approved
Comment: Corrections made. Electrical final approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/4/2024CorrectedCorrect following Item  Replaced stair well lighting and panelProvide access and coordination to open OCPD supplying stairway lighting to confirm circuit and function of all lights. Could not locate circuit while onsite. Checked various panel board locations. Verify circuit directory is up to date for new lighting. Ensure circuit is labeled for emergency lighting and location.
2/13/2024CorrectedCorrect following Item  Replaced stairway lighting.Stairway lights are required to be on an emergency generator or battery back-up.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS