Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 798314
Inspection Type: Electrical Rough
Inspector: O.Burbridge
Result: Cancel
Comment: Canceled by Chris.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/26/2024Transfer01See inspection comments 2nd floor roomsAFCI protection required at bath receptacles and must be readily accessible at headboard locations.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS