Inspection #: 796626
Inspection Type: Electrical Rough
Inspector: O.Burbridge
Result: Correction
Comment: 2nd floor rooms- see corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/26/2024Transfer01See inspection comments 2nd floor roomsAFCI protection required at bath receptacles and must be readily accessible at headboard locations.
1/26/2024Corrected01See inspection comments  3rd floor gutters feeding panels must be upsized to #10 conductors for 20A breakers.