Inspection #: 796317
Inspection Type: Ceiling Rough Electrical
Inspector: O.Burbridge
Result: Correction
Comment: 2nd floor corridor lid- see corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/5/2024TransferEC1Correct Below 2nd floor east sideJunction box for emergency lighting incomplete.
8/5/2024TransferEC1Correct Below 2nd floor east sideBond gutters with largest ground wire and provide covers and end caps.
8/5/2024TransferEC1Correct Below 2nd floor east sideReplace #12 conductors in flex between gutters and panels with #10 copper conductors and add #10 ground wire.
3/12/2024CorrectedEC1Correct Below 2nd floor west side ceiling Close gutters, secure mc cable at lobby, complete exit signs at west end, remove flex at old pull station, and provide support for communication wires.