Inspection #: 794894
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: See new corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/1/2024TransferCorrect Below*  Does voltage of service match requirements for TRUs?
8/1/2024TransferCorrect Below*  Label service with available fault current and date calculated.
8/1/2024TransferCorrect Below*  NEC 626.31(C) requires specific voltage/amperage ratings for receptacles. Installation does not match these requirements. Cords on TRUs do not match up with voltage, amperage, or pin configuration of installed receptacles.
8/1/2024TransferCorrect Below*  Physical protection required at Electrified truck service and receptacle pedestals.
3/4/2024TransferCorrect Below*  Heat trace requires labels and lockout on breaker.
3/4/2024TransferCorrect Below*  Label disconnects with source.
3/4/2024TransferCorrect Below*  30" width and 36" depth workspace required at exterior compactor controller.
3/4/2024TransferCorrect Below*  Compactor and baler require wire phasing.
2/1/2024TransferCorrect Below*  Platform required at rooftop condensing units so that centerline of disconnect handle is no greater than 6'7" above working platform.
2/1/2024TransferCorrect Below*  Shore power service and associated hook ups incomplete.
2/1/2024TransferCorrect Below*  Truck plugs at loading dock incomplete.
2/1/2024TransferCorrect Below*  Compactor disconnect requires bonding bushing.
2/1/2024TransferCorrect Below*  Conveyor system incomplete. Not all components appear to have a valid listing label. Field evaluation by a NRTL may be required.