Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 794483
Inspection Type: Underground Plumbing
Inspector: Y.Dovba
Result: Correction
Comment: Please address corrections and call for reinspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/30/2024TransferUnGrndPlumb11Corrections as FollowsMake corrections as followsUnderground gas piping serving outdoor patio heaters. southeast corner of the building. corner of 4th avenue and C street. (HDPE piping).Per 2018 IFGC local amendment 404.21 approved outdoor gas flexes to be installed at each end prior to entering the building proving 6'' inches of displacement.
7/30/2024TransferUnGrndPlumb11Corrections as FollowsMake corrections as followsUnderground gas piping serving outdoor patio heaters. southeast corner of the building. corner of 4th avenue and C street. (HDPE piping).Per 2018 IFGC section 404.17.1 plastic piping limitations: HDPE piping to be transitioned outside the building with a use an approved anodeless riser. (each gas outlet to be transitioned by using and anodeless riser) Per 2018 IFGC section 404.6 Gas piping must not penetrate the building/footing below grade. (above grade only)
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS