Inspection #: 792802
Inspection Type: Electrical Inspection
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/4/2024TransferCorrect following Item  Replaced stair well lighting and panelProvide access and coordination to open OCPD supplying stairway lighting to confirm circuit and function of all lights. Could not locate circuit while onsite. Checked various panel board locations with contractor rep. Verify circuit directory is up to date for new lighting. Ensure circuit is labeled for emergency lighting and location.
2/13/2024CorrectedCorrect following Item  Replaced stairway lighting.Stairway lights are required to be on an emergency generator or battery back-up.