Click Here To View Another Inspection Inspection #: 792683 Inspection Type: Electrical Rough Inspector: O.Burbridge Result: Partial Comment: Electrical rough for 2nd and 3rd floor rooms east of doorway approved. Inspection Corrections DateStatusCodeDescriptionRefLocationComments 1/26/2024Transfer01See inspection comments 3rd floor gutters feeding panels must be upsized to #10 conductors for 20A breakers.