Inspection #: 792503
Inspection Type: Ceiling Rough Electrical
Inspector: O.Burbridge
Result: Partial
Comment: Corrections made- ceiling electrical for 3rd floor approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/9/2024CorrectedEC1Correct Below  Exit signs require seismic support wires.
2/9/2024CorrectedEC1Correct Below  Wiring must be at least 1 1/2" beneath lowest part of pan decking of roof.
2/9/2024CorrectedEC1Correct Below  Each luminaire must be securely fastened to grid with 2 screws in opposite corners or 4 clips that connect to grid.
2/9/2024CorrectedEC1Correct Below  Close all junction boxes in ceiling.