| Date | Status | Code | Description | Ref | Location | Comments |
| 2/9/2024 | Corrected | EC1 | Correct Below | | | Exit signs require seismic support wires. |
| 2/9/2024 | Corrected | EC1 | Correct Below | | | Wiring must be at least 1 1/2" beneath lowest part of pan decking of roof. |
| 2/9/2024 | Corrected | EC1 | Correct Below | | | Each luminaire must be securely fastened to grid with 2 screws in opposite corners or 4 clips that connect to grid. |
| 2/9/2024 | Corrected | EC1 | Correct Below | | | Close all junction boxes in ceiling. |