Click Here To View Another Inspection


Inspection #: 791675
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/4/2024TransferCorrect Below*  Heat trace requires labels and lockout on breaker.
3/4/2024TransferCorrect Below*  Label disconnects with source.
3/4/2024TransferCorrect Below*  30" width and 36" depth workspace required at exterior compactor controller.
3/4/2024TransferCorrect Below*  Compactor and baler require wire phasing.
2/1/2024TransferCorrect Below*  Platform required at rooftop condensing units so that centerline of disconnect handle is no greater than 6'7" above working platform.
2/1/2024CorrectedCorrect Below*  Compressor A and C require max 200A overcurrent protection.
2/1/2024TransferCorrect Below*  Shore power service and associated hook ups incomplete.
2/1/2024TransferCorrect Below*  Truck plugs at loading dock incomplete.
2/1/2024TransferCorrect Below*  Compactor disconnect requires bonding bushing.
2/1/2024TransferCorrect Below*  Conveyor system incomplete. Not all components appear to have a valid listing label. Field evaluation by a NRTL may be required.
2/1/2024CorrectedCorrect Below*  Baler and compactor installation incomplete.