| Date | Status | Code | Description | Ref | Location | Comments |
| 2/1/2024 | Transfer | Correct Below | * | | | Platform required at rooftop condensing units so that centerline of disconnect handle is no greater than 6'7" above working platform. |
| 2/1/2024 | Transfer | Correct Below | * | | | Compressor A and C require max 200A overcurrent protection. |
| 2/1/2024 | Transfer | Correct Below | * | | | Shore power service and associated hook ups incomplete. |
| 2/1/2024 | Transfer | Correct Below | * | | | Truck plugs at loading dock incomplete. |
| 2/1/2024 | Transfer | Correct Below | * | | | Bailer and compactor disconnects require bonding bushings. |
| 2/1/2024 | Transfer | Correct Below | * | | | Conveyor system incomplete. Not all components appear to have a valid listing label. Field evaluation by a NRTL may be required. |
| 2/1/2024 | Transfer | Correct Below | * | | | Bailer and compactor installation incomplete. |