Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 791218
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: Cancel
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/29/2024TransferFire 16Correction(s) #3Please correct the following: Fire Smoke hatches need to be serviced and tested per discussion with Sean Pisoni with NRG Engineering this was suppose to be done with construction to meet the requirements of 2018 IFC 910.5 for annual inspection and 5 year operation.  Work to be completed no later than May 31 2024 with certification paperwork loading into MOA's LIVSafe tracking system. 
1/29/2024TransferFire 13Correction(s) #1Please correct the following: (1) North exit door to walk in cooler need adjusting.  Takes over 15 pound of force to open the door. (2) Walk in cooler exit lighting is not working completely.
1/29/2024TransferFire 15Correction(s) #2Please correct the following: Fire extinguishers (1) need additional 2 in front by checkout (2) relocate one in candy that is blocked (3) add additional in tobacco and liquor (4) reinstall fire extinguisher in area were the boxing machine is being setup. 
1/29/2024TransferFire 5FDC signProvide FDC sign at location visible from the street building is addressed on. Letters msut be a minimum of 6" high. Provide FDC sign over the fire department connection on northside of the building
1/29/2024TransferFire 9Knox keyFire Dept approved Knox Box required at Front Main Entry with keys to building for emergency responders.  Call 907-267-4950 for fire dispatch or 907-267-5006 Fire Station 6 to come install updated keys in the KnoxBox.