Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 790952
Inspection Type: Plumbing Rough
Inspector: E.Wood
Result: Correction
Comment: Gas piping and tests, for the cook line, the 12 middle tables in the dinning room, the water heater, and the main, Approved. SEE CORRECTIONS. NOTE: We will need to see the north wall and south wall gas tests at a later date.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/25/2024TransferPlumbRgh14CommentsSee Inspectors CommentsAll the building water piping.Per 608.2 of the 2018 UPC "Where static water pressure in the water supply piping is exceeding 80 PSI an approved-type pressure regulator preceded by an adequate strainer shall be installed and the static pressure reduced to 80 PSI or less. Pressure regulators equal to or exceeding 1 1/2" shall not require a strainer." The building pressure is 90 PSI and the entire building needs to be regulated down to 80 PSI or less.